Sonelite - Manufacturers of Bare copper wire, Tinned copper wire and Tinned copper fuse wire

Non standard fuse wire data obtain from Bhagirath Palace Electrical Market Association Dairy

Current rating of fuse
amp
Approximate fusing current
amp
Tinned Copper Wire
Size
(mm)
Size±Tolerance
(mm)
S.W.G Diameter Inch mm Size Min Max Min Max
1.5 3 40 .0048 0.122 0.119 0.124 1.5376 1.4194
2 4 39.9 .0050 0.127 0.124 0.130 1.4166 1.3076
2.5 4 39 .0052 0.132 0.129 0.135 1.3113 1.2105
3.0 5 38 .0060 0.152 0.149 0.155 0.9889 0.9129
3.5 6 37 .0068 0.173 0.169 0.176 0.7661 0.7072
4.5 7 36 .0076 0.193 0.189 0.197 0.6134 0.5662
5.0 8 35 .0084 0.213 0.210 0.217 0.4966 0.4677
5.5 9 34 .0092 0.234 0.230 0.238 0.4130 0.3890
6.0 10 33 .0100 0.250 0.246 0.254 0.3619 0.3408
7.0 11 32 .0108 0.274 0.270 0.278 0.3012 0.2837
8.0 12 31 .0116 0.295 0.291 0.298 0.2585 0.2474
8.5 13 30 .0124 0.315 0.312 0.318 0.2261 0.2164
10.0 16 29 .0136 0.345 0.341 0.349 0.1885 0.1804
12.0 18 28 .0148 0.376 0.372 0.380 0.1584 0.1522
13.0 23 27 .0164 0.416 0.412 0.420 0.1294 0.1231
14.0 28 26 .0180 0.457 o.453 0.462 0.1071 0.1017
15.0 30 25 .020 0.508 0.503 0.513 0.0866 0.0822
17.0 33 24 .022 0.559 0.553 0.564 0.0717 0.0680
20.0 38 23 .024 0.610 0.604 0.616 0.0602 0.0572
24.0 48 22 .028 0.711 0.704 0.718 0.0443 0.0420
29.0 58 21 .032 0.813 0.805 0.821 0.0339 0.0321
34.0 70 20 .036 0.914 0.905 0.924 0.0268 0.0252
38 81 19 .040 1.016 1.006 1.026 0.0217 0.0206
45 106 18 .048 1.219 1.207 1.231 0.0151 0.0143
65 135 17 .056 1.422 1.408 1.436 0.0111 0.0104
73 166 16 .064 1.626 1.610 1.642 0.0085 0.0080
78 197 15 0.072 1.829 1.811 1.847 0.0067 0.0063
102 230 14 .080 2.032 2.012 2.052 0.0054 0.0051
130 295 13 .092 2.340 2.317 2.363 0.00409 0.00383
- - 12 0.104 2.640 2.614 2.666 0.00321 0.00299
- - 10 0.128 3.250 3.218 3.283 0.00212 0.00194
- - 08 0.160 4.064 4.023 4.105 0.00136 0.00120